Liquid Cooling Piping System

Liquid Cooling Piping System

Factory-prefabricated primary and secondary piping, manifolds, dry quick couplings, sensors and coolant for cold-plate and immersion liquid-cooled data centers. Designed, built, tested and commissioned by ROCKERHILL as one system.
Rating: 4.7
(5 ratings)
Send Inquiry
Description

DN20–DN600

From cabinet branches to primary mains

≤ 1.6 MPa

Primary-side working pressure

100%

Factory inspected: 24 h pressure hold, ΔP–flow, cleanliness

Zero drip

Dry-break UQD couplings, hot-swap without draining

 

One supplier for the whole coolant path

 

Liquid cooling moves heat from high-density racks to the outdoors through two loops. The primary side carries facility water between cooling towers or chillers and the plate heat exchangers or CDUs. The secondary side carries clean coolant from the CDU through manifolds and quick couplings to the cold plates in each server. ROCKERHILL supplies every piece of hardware on that path, prefabricated and tested in the factory, so the machine room is assembled by number with almost no on-site welding.

 

SYSTEM LAYOUT

Loop

Coolant path

ROCKERHILL scope

Primary side

Cooling tower / chiller → plate heat exchanger / CDU

Carbon steel DN65–600, stainless steel DN50–300, sensors

Secondary side

CDU → manifold → UQD couplings → rack cold plates

Prefab piping DN50–300, branches DN20–40, manifolds, UQDs, sensors, coolant

 

Eight product lines, one system

 

01

Primary carbon steel piping

Mains from cooling towers and chillers to heat exchangers and CDUs. DN65–DN600, seamless steel, prefabricated.

02

Primary stainless piping

304 / 316L mains and machine-room sections where water quality matters. DN50–DN300, TIG welded, passivated.

03

Secondary prefab piping

CDU to manifold and cabinet distribution. Cut, welded, cleaned, assembled and 100% inspected in the factory.

04

Manifolds

Machined 304 / 316L valve blocks, 4–24 branches, four configurations M0–M3, branch flow preset.

05

UQD quick couplings

Dry-break cabinet connectors. Zero drip, keyed blind-mate, tool-free live replacement.

06

Sensors

Temperature, pressure, flow, level and water quality, delivered as complete monitoring modules.

07

Coolant

Ethylene glycol fluid for cold-plate loops and phase-change dielectric fluid for immersion cooling.

08

Delivery & O&M

Installation, flushing, pressure testing, commissioning and maintenance of the full system.

 

WHY ROCKERHILL

Almost no hot work on site

Secondary-side assemblies ship pre-assembled with manifolds and UQDs and are connected by number. Welding stays in the factory, where it can be controlled and inspected.

Tested before it ships

Every assembly gets a 24-hour pressure hold, a flow and pressure-drop check and a cleanliness check. Records travel in the box.

Balanced from day one

Manifold branch valves are preset by hydraulic calculation and each unit ships with its ΔP–flow curve, so no branch-by-branch balancing is needed on site.

 

Primary piping and fittings

 

Carbon steel

Parameter

Value

Nominal diameter

DN65 – DN600

Material

Q235B / 20# seamless steel pipe (GB/T 8163)

Connection

Welded or flanged; sections prefabricated in the factory

Working pressure

≤ 1.6 MPa

Corrosion protection

Shot blasting, epoxy zinc-rich primer + topcoat, film thickness per design

 

Stainless steel

Parameter

Value

Nominal diameter

DN50 – DN300

Material

304 / 316L (GB/T 12771); butt-weld elbows, tees, reducers

Welding

TIG, argon back-purged, full penetration with double-side bead

Inner surface

Pickled and passivated; hygienic Ra ≤ 0.8 μm optional

Working pressure

≤ 1.6 MPa

Certified welders, NDT of welds by proportion, endoscope checks of stainless weld roots, hydrostatic and ball-pass records archived by pipe-section number. Sections ship numbered for flanged assembly on site.

 

Secondary prefabricated piping assemblies

 

Parameter

Value

Nominal diameter

DN50 – DN300; cabinet branches DN20 – DN40

Material

304 / 316L stainless steel

Factory inspection

24 h pressure hold, flow / pressure-drop curve, particle-count cleanliness (100%)

Packaging

Pipe ends capped, number labels, inspection records in each box

Documents

Inspection records, ΔP–flow curve, product certificate

Design basis

Shop drawings from detailed BIM model of the machine room

 

Five factory processes

 

  • Cutting & bending. CNC bending; wall thickness and roundness checked to drawing.
  • Welding. Argon-arc stations with weld parameters recorded.
  • Cleaning & purging. Internal cleanliness accepted by particle count.
  • Assembly. Valves, sensor seats and labels pre-installed.
  • Final inspection. Pressure hold, flow pressure drop and cleanliness on every assembly.

 

product-756-399

TRACEABLE STAINLESS AND CARBON STEEL PIPE STOCK

Traceable from coil to cabinet

Every pipe section, manifold and sensor carries a code linked to its raw-material batch, process parameters and inspection records. One scan retrieves the full history; an abnormal material batch can be traced to the exact shipped boxes.

 

Manifold distributor

 

M0 · Basic

Manual ball valves; any branch can be shut off.

M1 · Metered

Branch temperature and supply/return ΔP monitoring.

M2 · Adjustable

Motorized branch valves linked to the CDU.

M3 · Smart

Per-branch flow measurement and control ports, per project.

Parameter

Value

Body

304 / 316L machined valve block

Branches

4 – 24, configured to the number of cabinets

Branch interface

UQD seat or G1/2 thread, to suit cabinet interface

Branch fittings

Manual ball valve; thermometer pocket and ΔP gauge port optional

Factory calibration

24 h pressure hold; per-branch ΔP–flow curve supplied

product-252-394

MACHINED STAINLESS MANIFOLD VALVE BLOCKS

 

UQD dry quick couplings

 

The cabinet connection point. The dry valve core shuts off both sides on separation, so cabinets and sensors can be serviced without draining the loop. Keyed ends make it impossible to swap supply and return. Compatible with common OCP UQD specifications.

 

Zero-drip disconnect

Dry core shuts off both ways

Blind-mate, error-proof

Keyed supply / return ends

Tool-free replacement

Hot-swap without draining

 

Parameter

Value

Nominal bore

DN19 (DN13 optional)

Valve core

Dry shut-off, zero drip on disconnect

Body / seal

Stainless steel; FKM seal (EPDM optional), selected for glycol or DI water

Mating cycles

≥ 1,000

Pressure / temperature

≤ 0.6 MPa; 0 – 60 °C

Options

Integrated sensor seat; pre-assembled on piping and manifolds

product-527-220

COLOR-CODED SUPPLY AND RETURN COUPLINGS

 

Liquid cooling sensors

 

Five measurement types cover the full monitoring scope of a liquid-cooling loop. The pressure transmitter uses a dry, oil-free ceramic capacitive cell with a 316L wetted diaphragm, which drifts less than diffused-silicon designs under year-round immersion in glycol or deionized water.

product-123-321

CERAMIC CAPACITIVE PRESSURE TRANSMITTER

Pressure transmitter

Value

Sensing cell

Ceramic capacitive, dry and oil-free; 316L wetted diaphragm

Range

0 – 1.0 MPa (0 – 0.6 MPa optional)

Accuracy

±0.5 %FS (±0.25 %FS optional)

Overload / drift

3 × FS; ≤ ±0.1 %FS per year

Temperature

Media −10 to 70 °C; ambient −20 to 60 °C

 

Measurement

Requirement (GB/T 48023-2026 §9.4)

ROCKERHILL configuration

Covered

Temperature

Supply / return temperature

Complete temperature points

✓

Pressure

Supply / return pressure, filter ΔP

Pressure transmitters ±0.5 %FS

✓

Flow

Supply / return flow, class 0.5 meter

Complete flow points

✓

Level

Make-up tank and system level

Level sensors

✓

Water quality

pH, conductivity, turbidity

Conductivity / turbidity points + water-quality service

✓

 

COOLANT

Cold-plate ethylene glycol fluid

Formulated, filled and concentration-tested with the piping system. Top-up and replacement advice follows conductivity, pH and turbidity trends, with test records kept per project.

Immersion phase-change fluid

Dielectric fluid with adjustable boiling point of 50–55 °C and dielectric constant below 2.0, for two-phase immersion cooling. Supplied with a material compatibility test report.

 

Where the system is used

 

Facility

Typical scope

AI and HPC data halls

High-density GPU racks on cold plates: full primary and secondary piping, M2 / M3 manifolds with per-branch monitoring

Colocation and cloud

Liquid-cooled rows alongside air-cooled space; prefabricated secondary loops and UQD-connected cabinets for fast tenant fit-out

Retrofit of air-cooled rooms

Weld-free secondary assemblies installed in live rooms with minimal hot work and disruption

Immersion cooling

Phase-change dielectric fluid, piping and water-quality service for immersion tanks

Edge and modular data centers

Compact factory-built loops shipped pre-tested inside containers and prefabricated modules

 

From factory to commissioned system in four steps

 

01 · DESIGN

BIM shop drawings

Pipe routing checked in advance against civil works and cable trays.

02 · FABRICATE

Pre-assembly & full test

Piping pre-assembled with manifolds and UQDs; pressure and cleanliness tested.

03 · SHIP

Numbered delivery

Sections connected on site by number; secondary side essentially weld-free.

04 · COMMISSION

Flush, test, hand over

Flushing, venting, pressure hold and water quality, with records in the box.

 

What we check before handover

 

Item

Typical acceptance value

Instrument

Cleanliness

NAS class 7 (ISO 18/16/13) after flushing; stable end-filter ΔP

Online particle counter, membrane weighing

Tightness & pressure hold

1.0 MPa for 30 min, no visible leak; ≤ 5% drop over 24 h

Test pump, pressure recorder, IR camera

Vacuum & moisture

−0.09 MPa held; dew point ≤ −20 °C before filling

Vacuum pump, dew-point meter

Water quality

Conductivity ≤ 10 μS/cm, pH 7–9, Cl⁻ ≤ 10 ppm; glycol to design (e.g. 25–30%)

Conductivity / pH meter, refractometer

Flow & ΔP

Branch flow deviation ≤ ±10%; system ΔP within design range

Ultrasonic flow meter, ΔP gauge

Temperature & alarms

Supply temperature ±1 °C; level, leak, ΔP and over-temperature alarms 100% triggered

Temperature logger, interlock test sheet

Typical values. Final criteria follow the project design documents and technical agreement.

 

product-1536-1024

ROBOTIC LASER WELDING

product-463-219

PRIMARY PIPE PREFABRICATION

product-463-214

CNC MACHINING OF VALVE BLOCKS

product-1603-301

Planning a liquid-cooled data hall?

Send us your rack count, heat load per rack, CDU arrangement and machine-room layout. Our engineers will return a sized piping and manifold proposal with a bill of materials.