1. Product Overview
An Air Cooled Heat Exchanger (ACHE), also known as a fin-fan cooler or air-cooled condenser, is a heat transfer device that uses ambient air instead of cooling water to remove heat from a process fluid. The hot fluid flows inside finned tubes, while fans force or draw large volumes of ambient air across the outside of the tube bundle, cooling or condensing the fluid.
As a equipment manufacturer, ROCKERHILL designs and manufactures air cooled heat exchangers as stand-alone units or as part of complete process skids and water treatment, desalination and gas processing packages. Rockerhill has deep knowledges from project operations and technical optimization.
2. Working Principle
Process fluid enters the inlet header box, passes through the finned tube bundle in one or more passes and leaves through the outlet header. Axial-flow fans move ambient air across the extended-surface (finned) tubes. Heat is transferred from the fluid, through the tube wall and fins, to the air. Fan speed, blade pitch or louvers can be adjusted to control the process outlet temperature as the ambient temperature and process load change.
Forced draft: Fans blow air upward through the bundle from below; the bundle is placed above the fans. Simple access to fans and drives, lower motor temperature exposure.
Induced draft: Fans pull air upward through the bundle from above; the bundle is placed below the fans. Better air distribution, lower hot-air recirculation and some protection of the bundle from weather.
3. Key Features
Water-free cooling: No cooling-water supply, treatment, blowdown or cooling tower plume; ideal for arid, remote and offshore sites.
Design to international standards: Rockerhill can design according to international standards, for example API Standard 661 / ISO 13706, with pressure parts to ASME VIII Div. 1, GB/T 151 or EN 13445 as specified by the project.
High thermal efficiency: Extruded, embedded or L-foot aluminum fins on carbon steel, stainless steel or alloy tubes give a large extended surface in a compact bundle.
Flexible configuration: Horizontal, A-frame or V-frame; forced or induced draft; single or multiple bays; with steam coils, louvers, recirculation or humidification for severe climates.
Precise outlet temperature control: Auto-variable pitch fans, VFD-driven motors, louvers and multi-fan staging.
Low operating cost: Low maintenance, no water-side fouling, optimised fan power and low-noise options.
Corrosion-resistant options: Galvanized or stainless steel structure, duplex / titanium / Cu-Ni tubes and epoxy or phenolic coatings for chlorides, sour service and coastal environments.
Skid-mounted supply: Can be delivered as a pre-assembled module with piping, instruments and control panel to reduce site work.And this is Rockerhill's strength and expertise.
4. Technical Parameters
The table below lists the typical design range. Each unit is custom-engineered to the project data sheet; values outside the range can be considered on request.
|
Parameter |
Typical Specification |
Remarks |
|
Heat duty (per unit) |
50 kW – 50 MW |
Multiple bays / units for larger duty |
|
Configuration |
Horizontal, A-frame, V-frame, vertical (steam condenser) |
Per process and layout |
|
Air flow arrangement |
Forced draft / induced draft |
|
|
Tube-side design pressure |
Full vacuum – 15 MPa(g) |
Higher pressure on request |
|
Tube-side design temperature |
-45 °C to 400 °C |
Special alloys for higher temperature |
|
Process fluids |
Hydrocarbons, gases, steam, process water, glycol, amine, oil, CO2, brine/condensate |
Single phase or condensing |
|
Tube outside diameter |
25.4 mm (1") / 31.75 mm / 38.1 mm |
Per API 661 |
|
Tube wall thickness |
1.65 – 3.4 mm (BWG 16 – 10) |
Per pressure and corrosion allowance |
|
Tube length |
3 m – 15 m |
Limited by shipping / site |
|
Tube rows |
3 – 10 rows (typically 4 – 6) |
Staggered (triangular) pitch |
|
Tube-side passes |
1 – 12 |
|
|
Fin type |
Extruded / embedded (G-fin) / L-foot / LL-foot / galvanized steel serrated |
Choice depends on max. fin temperature |
|
Fin pitch |
7 – 12 fins per inch (276 – 472 fins/m) |
|
|
Fin height / thickness |
9.5 – 16 mm / 0.35 – 0.5 mm |
|
|
Fan diameter |
0.9 m – 6.0 m |
Number of fans per bay: 1 – 3 |
|
Fan blades |
3 – 8 blades; FRP or aluminum alloy; fixed or auto-variable pitch |
|
|
Fan drive |
Direct drive, V-belt or gear reducer |
Motor 2.2 – 110 kW, IP55 / Ex-proof |
|
Capacity control |
VFD, auto-variable pitch, louvers, fan on/off staging |
|
|
Design ambient air temperature |
-40 °C to +55 °C |
Altitude and humidity corrected |
|
Min. approach temperature |
Approx. 10 – 15 K (process outlet – ambient air) |
Depends on economic design |
|
Noise level |
≤ 85 dB(A) at 1 m (standard); low-noise fans available |
Per project requirement |
|
Wind / seismic design |
Per local code and project specification |
|
|
Surface protection |
Hot-dip galvanizing, epoxy / polyurethane paint, special coatings |
Corrosive or coastal sites |
|
Area classification |
Safe area, Zone 1 / Zone 2 (IIA, IIB, IIC), Class I Div. 1 / 2 |
Ex-proof motors and instruments |
5. Materials of Construction (customization available)
|
Component |
Standard Material |
Optional / Upgrade Material |
|
Tubes |
Carbon steel A179 / A192 / A106 |
Stainless steel 304L/316L, duplex 2205, Cu-Ni, titanium, Monel |
|
Fins |
Aluminum 1060 / 1100 (extruded or wound) |
Galvanized steel, stainless steel, copper |
|
Header boxes |
Carbon steel A516 Gr.70 / Q345R |
Stainless steel, duplex, cladding, inner lining |
|
Tube sheets / plugs |
Carbon steel A516 Gr.70 |
Stainless steel / alloy cladding or overlay |
|
Nozzles & flanges |
A105 / A106 / A350 LF2 |
Stainless steel, duplex, alloy |
|
Structure & plenum |
Carbon steel Q235B / A36, painted |
Hot-dip galvanized, stainless steel |
|
Fan blades |
Aluminum alloy |
FRP (GRP), carbon-fiber reinforced |
|
Fan guard / louvers |
Galvanized steel / aluminum |
Stainless steel |
6.Application Areas
(customization available)
|
Industry |
Typical Services |
Typical Process Fluid |
|
Oil & gas / refining |
Overhead condensers, product and crude coolers, reflux condensers, lube-oil coolers |
Hydrocarbons, naphtha, diesel, lube oil |
|
Natural gas processing & LNG |
Compressor inter/after coolers, gas coolers, propane / refrigerant condensers, amine and TEG coolers |
Natural gas, refrigerants, amine, glycol |
|
Petrochemical & chemical |
Process cooling and condensing, reactor effluent coolers, solvent condensers |
Solvents, chemical vapors, process liquids |
|
Power generation |
Air cooled steam condensers, closed-loop cooling water (dry coolers), generator and turbine oil cooling |
Steam, water-glycol, lube oil |
|
Carbon capture & CO2 processing |
CO2 compressor after-coolers, CO2 liquefaction pre-cooling, solvent coolers |
CO2, MEA / amine, wet gas |
|
Mining & minerals |
Hydrometallurgical process cooling, leach solution coolers, compressor coolers in arid regions |
Acid / process solutions, air, water |
|
Water treatment & desalination |
MVR / evaporator vapor condensate cooling, brine and concentrate cooling, process water recovery, skid-mounted heat rejection |
Hot water, condensate, brine |
|
Sugar, alcohol, pulp & paper |
Vapor and condensate cooling, hot-process liquid cooling where water is limited |
Vapor, juice, spent liquor |
|
Biogas, hydrogen & renewable energy |
Biogas and hydrogen compression coolers, electrolyser cooling, solar thermal heat rejection |
Biogas, H2, water-glycol |
|
Data center, HVAC & industrial cooling |
Dry coolers for chilled-water and closed-loop systems, free cooling |
Water, glycol solution |
|
Marine & offshore |
Topside process and utility cooling with corrosion-resistant materials |
Process fluids, glycol |
7. Standards, Quality & Testing
API 661 / ISO 13706 (air-cooled heat exchangers for general refinery service).
ASME Section VIII Div. 1, GB/T 151, GB 150, EN 13445 or other pressure vessel code as required by the project.
Welding procedure and welder qualifications per ASME IX or equivalent; NDE (RT / UT / MT / PT) as per specification.
Hydrostatic test of tube bundles; pneumatic leak test where required; fan balancing and run test; vibration check.
Third-party inspection (SGS, BV, TÜV, Lloyd's or client nominated) can be arranged on request.
Documentation package including material certificates (EN 10204 3.1) and final dossier.
8. Why ROCKERHILL
Integrated design, engineering, procurement, manufacturing and project delivery in one team, with a 17,000 m² manufacturing hub in Jiangsu, China.
Operating Project references globally including America and middle east.
Ability to supply the air cooler together with the surrounding process skid, pumps, valves and water treatment equipment.
Fast technical response, multilingual support (English, Chinese, Spanish, German, French).
18-month warranty and long-term after-sales support.
We're professional air cooled heat exchanger manufacturers and suppliers in China, specialized in providing high quality custom service. We warmly welcome you to buy high-grade air cooled heat exchanger at competitive price from our factory.